CENTRAL VACUUM SYSTEM INSTALLATION REQUIREMENTS

ELECTRICAL SERVICE

Line Voltage - Three Phase
Provide separate 208, 230, 460 or 575 volt 3-phase electrical circuit for each vacuum turbine. The voltage your turbine motor will operate on is determined by the main line voltage installed in your building.

Line Voltage - Single Phase
Provide separate 208 or230 volt single-phase electrical circuit for each vacuum turbine. The voltage your turbine motor will operate on is determined by the main line voltage installed in your building. You can operate up to a 10 H.P. motor, as long as you have enough amperage service.

TURBINE MOTOR ELECTRICAL WIRING

Wire size necessary for vacuum turbine motor operation will be determined by motor H.P., phase, volts, full load amps and distance from circuit breaker panel location. Refer to power flow turbine literature for requirements based on model selected.

TURBINE MOTOR RUNNING PROTECTION

Provide a across the line non-reversing magnetic starter with auxiliary contact sized for H.P., voltage, phase and full load amps of each motor. When starter is installed indoors, use NEMA 1 enclosure, outdoors use NEMA 3R enclosure.

TURBINE MOTOR DISCONNECT

Provide fused disconnect for each turbine motor, sized for H.P., voltage, amps and phase. NEMA 1 enclosure indoors, NEMA 3R enclosure outdoors. Disconnect not necessary if electrical circuit breaker panel is accessible at vacuum turbine location.

TURBINE MOTOR ON-OFF OPERATION

Provide weather-tight on-off push button control switch at vacuuming location for each vacuum turbine. Run 3 #14 THHN wires from each turbine magnetic starter to each on-off control switch location. Use explosion proof on-off push button control in hazardous locations, such as near gas dispensers.

VACUUM EQUIPMENT FOUNDATION

Always install vacuum turbine(s) and debris separator on a solid foundation. Concrete is preferred, as it provides a solid base. When equipment is installed in a wet environment, we recommend a pad 4" to 6" high be poured to elevate equipment and protect it from standing water and/or moisture.

VACUUM TURBINE VENTILATION

Indoors
When vacuum turbine is installed indoors, provide adequate ventilation such as outside to inside air duct, wall vents, roof turret vents, or louvered door or doors, and exhaust fan controlled via a thermostat to turn on fan at 850F. Fan should be sized to turn air over in every room every 15 minutes minimum.

Outdoors
When vacuum turbine is installed outdoors and enclosed for weather protection, follow indoor requirements. Never install vacuum turbine in an enclosure without adequate ventilation and turbine exhaust to atmosphere. When installed outdoors in cold climates, also install one 100 watt light bulb controlled by a thermostat set to come on at 400 F and off at 550 F.

VACUUM TURBINE EXHAUST

Always exhaust vacuum turbine with 4" IPS pipe to atmosphere when installed indoors, or when installed outdoors in a weatherproof enclosure. If exhaust pipe exceeds 20' total distance, run 6" IPS pipe total distance. Always protect exhaust pipe termination from the elements.

When exhausted through the roof, install a 900 elbow and 450 elbow on end of pipe. When exhausted through sidewall, install 450 elbow on end of pipe pointed toward ground. When vacuum turbine is installed outdoors with no enclosure, install 900 elbow and 450 elbow on exhaust silencer, 4" discharge fitting.

VACUUM PIPING SYSTEM - VEHICLE CARE, CAR WASH, DETAIL AND NEW CAR DEALER

RECOMMENDED PIPE AND FITTINGS ABOVE GROUND

ABS, PVC, DWV or Zinc-coated steel

PIPING SYSTEM OVERHEAD

Support from under canopy type structure, building ceiling or walls, or construct overhead support structure for vacuum piping system outside in the open

PIPING SYSTEM BELOW GROUND

Use 4" no. hub metal pipe and fittings for best results and to prevent cracking and wear.

PIPING SYSTEM DIMENSION REQUIREMENTS

Vacuum piping system's overhead should be a minimum of 10 ft. from ground level and pipe drops for hose connections should be a maximum of 6.5 ft. to 7.0 ft. from ground level. THese dimensions may need to be adjusted depending on vehicle clearance needed and accessibility for employees. Distance between hose drops (abreast) should be a minimum of 12.0 ft. for vehicle side clearance and 20.0 ft. apart when vehicles are placed one behind the other.

PIPING SYSTEM SUPPORTS OVERHEAD

Support piping systems every six feet maximum to prevent sagging. Very important when using ABS or PVC outside exposed to elements. For best support and to eliminate excessive movement of drops, we recommend using unistruct (channel iron) with clamps sized for outside diameter (O.D.) of pipe used. If pipe must be hung from ceiling, use 3/8" allthread  and pipe hangers sized for pipe used. It may be necessary to sway brace to prevent excessive movement.

PIPING SYSTEM KITS

Vacutech LLC can provide complete kits consisting of: Pipe, Fittings, Glue, Hardware and Hangers.

DESIGN

Fax or mail a sketch of your vacuum system layout with dimensions of vacuum equipment location to first hose drop, distance between drops, and height you would like overhead mainline. We will provide an isometric drawing with material needed (approx.) for your system requirements.